From: Planning
Sent: 30 January 2008 17:17
To: Janet Reason
Subject: FW: 3rd Party Planning Application - 07/02291/OUT - amended plans
 
 

Helen Hicks
Administrator
Planning, Housing and Economy
Cherwell District Council

Ext:  1884
Direct Dial:  01295 221884

mailto:  helen.hicks@cherwell-dc.gov.uk
www.Cherwell-dc.gov.uk

 


From: DevconTeam@thameswater.co.uk [mailto:DevconTeam@thameswater.co.uk]
Sent: 30 January 2008 14:07
To: Planning
Subject: 3rd Party Planning Application - 07/02291/OUT - amended plans

Cherwell District Council
Planning & Development Services
Bodicote House
Bodicote, Banbury
Oxon
OX15 4AA

30 January 2008 
Our DTS Ref: 1097
Your Ref: 07/02291/OUT - amended plans 

Dear Sir/Madam

Re: HEYFORD PARK, CAMP ROAD, UPPER HEYFORD, BICESTER, OXFORDSHIRE, OX25

Waste Comments
Following initial investigation, Thames Water has identified an inability of the existing waste water infrastructure to accommodate the needs of this application. Should the Local Planning Authority look to approve the application, Thames Water would like the following 'Grampian Style' condition imposed. "Development shall not commence until a drainage strategy detailing any on and/or off site drainage works, has been submitted to and approved by, the local planning authority in consultation with the sewerage undertaker. No discharge of foul or surface water from the site shall be accepted into the public system until the drainage works referred to in the strategy have been completed". Reason - The development may lead to sewage flooding; to ensure that sufficient capacity is made available to cope with the new development; and in order to avoid adverse environmental impact upon the community. Should the Local Planning Authority consider the above recommendation is inappropriate or are unable to include it in the decision notice, it is important that the Local Planning Authority liaises with Thames Water Development Control Department (telephone 01923 898072) prior to the Planning Application approval.


Surface Water Drainage - With regard to surface water drainage it is the responsibility of a developer to make proper provision for drainage to ground, water courses or a suitable sewer. In respect of surface water it is recommended that the applicant should ensure that storm flows are attenuated or regulated into the receiving public network through on or off site storage. When it is proposed to connect to a combined public sewer, the site drainage should be separate and combined at the final manhole nearest the boundary. Connections are not permitted for the removal of Ground Water. Where the developer proposes to discharge to a public sewer, prior approval from Thames Water Developer Services will be required. They can be contacted on 0845 850 2777. Reason - to ensure that the surface water discharge from the site shall not be detrimental to the existing sewerage system.

Thames Water would recommend that petrol / oil interceptors be fitted in all car parking/washing/repair facilities. Failure to enforce the effective use of petrol / oil interceptors could result in oil-polluted discharges entering local watercourses.


Water Comments
The existing water supply infrastructure has insufficient capacity to meet the additional demands for the proposed development. Thames Water therefore recommend the following condition be imposed: Development should not be commenced until: Impact studies of the existing water supply infrastructure have been submitted to, and approved in writing by, the local planning authority (in consultation with Thames Water). The studies should determine the magnitude of any new additional capacity required in the system and a suitable connection point. Reason: To ensure that the water supply infrastructure has sufficient capacity to cope with the/this additional demand.

Thames Water recommend the following informative be attached to this planning permission. Thames Water will aim to provide customers with a minimum pressure of 10m head (approx 1 bar) and a flow rate of 9 litres/minute at the point where it leaves Thames Waters pipes. The developer should take account of this minimum pressure in the design of the proposed development.


Supplementary Comments
Discussions have taken place with the developer and stakeholders generating a number of options and these would to varying degrees be subject to approved funding under PR09 (period 2010-2015) by Ofwat the Regulator. The outcome of this process will have an influence on the final solution strategy.






























Yours faithfully

Development Planning Department

Thames Water
Development Planning
Maple Lodge
Denham Way
Rickmansworth
Herts WD3 9SQ
Tel: 01923 898072 
 

This is an automated email, please do not reply to the sender. If you wish to reply to this email click on the link below.
devcon.team@thameswater.co.uk
______________________________________________________________________

Why not collect rain in a water-butt for use in your garden? Visit www.thames2u.com or call 0845 658 0055 to order a 190-litre water-butt at a discounted price of just £24.95 including home delivery. Please quote reference number TW01 when ordering. (This offer applies to Thames Water customers only.)

Thames Water Limited (company number 2366623) and Thames Water Utilities Limited (company number 2366661) are companies registered in England and Wales each with their registered office at Clearwater Court, Vastern Road, Reading, Berkshire, RG1 8DB. This email is confidential and intended solely for the use of the individual to whom it is addressed. Any views or opinions presented are solely those of the author and do not necessarily represent those of Thames Water Limited or its subsidiaries. If you are not the intended recipient of this email you may not copy, use, forward or disclose its contents to any other person; please notify our Computer Service Desk on +44 (0) 118 959 3587 and destroy and delete the message and any attachments from your system.

For more information on Thames Water visit our web site at http://www.thameswater.co.uk